DPC- L(10/20)
manual
brochure
Product specification
1 point of pressure sensor
- Multi-type refrigerator operation control
- 3 output contacts
- Built-in low pressure ON/OFF delay timer
- Alternating Control
- Set pressure value can be input in units of 0.1 kgf/cm2
- Pressure unit (kgf/㎠, Mpa, Bar, Psi) Optional when ordering
power supply | 100-240V~ ±10%, 50-60hz(24VDC Order Specification) |
---|---|
current consumption | 200mA |
display | 3 Digit FND x 2 |
pressure range | -1.0~10, 20Kgf/㎠ |
output contact | SPDT 250V/ 3A |
commercial temperature | -20~60℃ RH 60% |
Sensor precision | 0.5% |
Communication application (Option) | RS-485 |
Current output application (Option) | 4-20mA |
Refrigerant gas selection | Refrigerants other than (R22, 23, 134, 404, 407, 410, 507 refrigerant temperature conversion function applied) can be ordered. |
Application Installation Diagram
Installation Type Chart