Digital pressure switch.

Digital pressure switch.

MPC SERIES

MPC-HLW (cooler, air dryer only)

  • brochure

Product specification

    3 pressure sensors (low pressure/high pressure/water pressure)

    - Low pressure 2 points, high pressure 1 point, water pressure 1 point, fan control 2 points

    - Built-in low pressure ON/OFF high pressure ON delay timer

    - Set pressure value can be entered in units of 0.1 kgf/cm2

    - Built-in pressure unit conversion mode (kgf/cm2, Mpa, Bar, Psi)

power supply 100-240V~±10%, 50-60hz (24VDC order specification)
current consumption 200mA
display C.LCD & B/L (Blue)
pressure range -1.0~50 Kgf/㎠ (Both Low & High,AIR(WATER))
output contact SPST 250V/ 3A
SPDT 250V/ 3A
commercial temperature -20~60℃ RH 60%
Sensor precision 0.5%FS
Communication application (Option) RS-485
Current output application (Option) 4-20mA
Refrigerant gas selection Refrigerants other than (R22, 134, 404, 407, 410, 507) are ordered specifications.

Application Installation Diagram


     

Installation Type Chart